Skip to the picture
Generator labLab
← Generator lab

Part 1 · The idea

  1. 1Split any three
  2. 2Three circuits

Part 2 · Faults in real systems

  1. 3The four faults
  2. 4Grounding
  3. 5Transformers & the line

Part 3 · Protecting the system

  1. 6The fault recorder
  2. 7What relays see
  3. 8Clear it in time

Teacher guide

The bus and its neutral

Dotted: the ground return. Press the meter to read it.

Voltages to ground

Picture

Where the fault current returns

Intermittent-arc overvoltages are not modelled. They are the reason for the IR ≥ IC rule.

What ground current buys, and what it costs

More ground current buys

    …and costs

      Zero network

      Numbers
      QuantitypuReal units

      In the voltage triangle, ground sits at g = −V0 = z0·E ÷ (z0 + z1 + z2 + 3Rf) from the centre: an arc from the centre (Rf → ∞) to the faulted corner (Rf = 0). It is a semicircle only when the zero path is purely capacitive.

      Why generator neutrals use high resistance

      Generator neutrals are usually grounded through a high resistance. A generator's own X0 is tiny, so solid grounding would make its ground faults the largest of all (chapter 3 shows the line-to-ground fault growing as X0 falls). Its step-up transformer's delta also keeps the line's ground faults away from it (chapter 5 shows why).

      Neutral
      Fault on phase